Wireless Protocol

EnOcean

Measurement Range

Temperature 0ºC to 40ºC

Humidity 0%R.H. to 100%R.H.

Accuracy

+/-0.5ºC between 17°C and 27°C

+/- 1°C between 0°C and 17°C

+/- 1°C between 27°C and 40°C

+/-5% R.H. Between 30% - 70% R.H. 0-40°C

Transmission Rate (Dynamic)

100 seconds if Temperature change > 0.5°C or
Humidity change > 2%

Else every 15 minutes

Battery Life* (Battery Back-up only)

Up to 10 Years

Battery Type (Battery Back-up only)

CR2354

Repeater

No

Telegram

4BS

Environment

Indoor

Enclosure Material

PC-ABS

Calibration

Factory Calibrated

Operating Temperature Range

-20ºC to +60ºC

Storage Temperature Range

-20ºC to +60ºC

Dimensions

76.5mm x 28mm x 17.5mm approx

EEP

A5-04-01


*Typical life expectancy of the battery is dependent on ambient light conditions and use-case.