Measurement Range 60A 3 Channel CT Clamp

1A-60A

Measurement Range 200A 3 Channel CT Clamp

2A-200A

Measurement Range 600A 3 Channel CT Clamp

2A-600A

Measurement Frequency

50Hz or 60Hz


Accuracy - whichever is greater

60A = +/- 0.1A or 2%  
200A = +/- 0.1A or 2.5%  
600A = +/- 1A or 3%  

Transmission Rate

30 Seconds

Reported Value

3 Separate channels in Amps

Repeater

No

Environment

IP 4X

Enclosure Material

Nylon 66

Sample time

Average of 5 measurements
per 30 seconds (Per channel)

Telegram

VLD

Calibration

Not Required

Operating Temperature & Humidity Range

-5°C to +40°C; 0%-85% RH

Storage Temperature & Humidity Range

-20°C to +55°C; 0%-85% RH

Diameter of Measurable Conductor 60A 3 Channel CT Clamp

10mm or less

Diameter of Measurable Conductor 200A 3 Channel CT Clamp

24mm or less

Diameter of Measurable Conductor 600A 3 Channel CT Clamp

36mm or less

Dimensions of 60A 3 Channel V3 CT Clamps

25mm x 22mm x 35mm approx.

Dimensions of 200A 3 Channel V3 CT Clamps

35mm x 45mm x 65mm approx.

Dimensions of 600A 3 Channel V3 CT Clamps

65mm x 41mm x 85mm approx.

Dimensions of Case

80mm x 55mm x 20mm approx.

EEP

D2-32-02