Pressac Sensing version 3 CT Clamp RJ11 leads must be securely connected to the sender units RJ11 sockets. Channel numbers are printed on the product label on the Pressac Sensing version 3 sender unit.

The Pressac Sensing Single Channel CT Clamp version 3 needs to be commissioned before use. There are 2 ways in which the unit can be commissioned.

  1. Self-powered learn
    As the unit is 100% energy harvesting, it can only perform a self-powered learn if it is clipped around a conductor and the minimum required current is flowing. (See below table)

Single Channel CT Clamp V3 Versions

Frequency

Minimum Current Required For Commissioning and Reporting

Current Reading Cap

60A Version

868MHz 902MHz 928MHz

1A Flowing

65A


Clip the CT clamp around the conductor and wait for a period of 30 seconds. Depress the learn button which is on the sender unit. The LED should briefly flash. The Version 3 Pressac Sensing Single Channel CT Clamp is now commissioned.


  1. Manual registration.

Alternatively, the unit can be commissioned onto your EnOcean network manually. To do this you will need the unique EnOcean ID of the Pressac Sensing Single Channel CT Clamp and also its EnOcean Equipment Profile (EEP). The EnOcean ID and the EnOcean Equipment Profile (EEP) are printed on the product label on the Pressac Sensing version 3 CT Clamp.


To be able to measure the current flowing within a single conductor, the Pressac Sensing version 3 CT Clamp must be correctly clipped around the single conductor, ensuring that the ferrite cores within the clamp reliably and consistently touch each other. In permanent installations, the unit can be cable tied to the conductor for added security.


Once installed and commissioned, the value of electric current is transmitted every 30 seconds. If a current lower than the minimum current required (see above table) is flowing, the Pressac Sensing version 3 CT Clamp will not report any information or transmit any EnOcean telegrams.


The product uses an EnOcean STM300 Module for transmitting the data wirelessly. It supports the following EEPs (EnOcean Equipment Profiles):

EEP D2-32-00